On Tue, 18 Feb 1997 15:15:16 -0600 (CST),
"The Great Mr. Kurtz [David A. Gatwood]" <davagatw@Mars.utm.edU> wrote:
> 1. What VA rating would you suggest to achieve that (the system's power
> supply is rated at 3 amps max, no idea what the real drain is, though),
You mean VAh? But sorry, I can't say anything about this.
> 2. How hard is it to set up LAN signalling on a free unix clone (i.e. is
> powerd or the equivalent available in source code form, and if not, how
> hard would something like that be to write)?
This is not so hard. I once did an instant automatic shutdown wiring
for a Pentium CGI server I set up for some fuel company's Web-based
polling system. It was running FreeBSD 2.1.0, though.
Anyway, the APS' UPS we used had an RS232-level signal output which
got grounded when the AC power went down. I connected the signal to
one of the serial port, and wrote a small daemon which periodically
polled for the status of the line. If it went down, the daemon would
bring the server down by "shutdown -h now". We never had to really
use it during the Web-polling operation, but I tested it a couple of
times (yanked the plug out) and it worked beautifully.
Hope this helps,
Ken